iCM500

Fume Cupboard Controller

  • Fume Cupboard Controller
  • Various applications of iCM500
  • iCM500 different modes
Product description

Variable microcontroller system for controlling and monitoring the exhaust air volume flow or the face velocity of fume cupboards as a function of the vertical and horizontal sash position.

The integrated function monitoring according to DIN EN 14175-6 provides maximum safety for the laboratory staff. An optical and acoustic alarm on the display of the iCM500 are triggered if the value falls below the respective setpoint value for exhaust air. The standard model is suitable for all types of fume cupboards and extractor systems. The standard model is delivered ex-factory with an airflow sensor.

Special features

Variable microcontroller system for fume cupboards
With 2.8″ full color display 320 x 240 pixels 7 18 bits
Parameterization and retrieval of all system values via user interface or software PC2500
Airflow sensor for measuring the face velocity
Integrated function moitoring of safe fume cupboard operation according to DIN EN 14175-6
Optical and acoustic alarm in case of malfunctions
Optical warning for the operating state “sash position >50 cm open”
High-speed algorithm
Reaction time and upward control of the exhaust air volume flow ≤ 2 s (Vmin to Vmax)
Orientation independent differential pressure sensor 4 to 300 PA for measuring the exhaust air volume flow [m³/h]
Functional description

The fume cupboard controller iCM500 constantly compares the actual values determined by the sensors used and controls the preset nominal value quickly and precisely.

The advanced extract air demand request immediately calculates the demand for extract air and provides this directly as a setpoint for the central extract air system. This decisively improves the control time of the room air control system (e.g. VAV supply air volume controller by SCHNEIDER Elektronik).

Advantages of the variable fume cupboard control depending on the sash opening height

The breakout protection from toxic substances of the fume cupboard in combination with minimum air consumption is guaranteed at each sash position. The sturdiness of the fume cupboard operation in terms of air ventilation is achieved by suitable parameter setting of the constant face velocity and can be adapted to any fume cupboard designs.

The device iCM500 checks the three sensors for plausibility and the correlation between the actual values of the differential pressure sensor, airflow sensor and sash position sensor. This constitutes a substantial improvement of the safety for the entire control system and for the user. Measuring errors and deviations are detected immediately and signaled by an alarm.

Related datasheets

Application areas

Icon Kolben, Symbol für Standardlabor

Standard laboratory

Icon Barett, Symbol für Trainingslabor

Training laboratory

Icon Dusche, Symbol für Reinraum

Clean room

Icon Biohazard, Symbol für Nuklidlabor

Nuclid laboratory

Icon Spritze, Symbol für Tierlabor

Animal laboratory

Function indicator
Optical and acoustic alarm for too low exhaust air
Optical display for sufficient exhaust air
Numeric display of the face velocity in m/s or ft/min;
or volume flow in m³/h or l/s; or pressure in Pa or mBar
Optical warning for the operating state „sash position
> 50 cm open“
Button for acknowledging the acoustic alarm
Button for control ON/OFF
Button for light ON/OFF (internal illumination of fume
cupboard)
Integrated user interface for parameterization
Connector for parameterization via laptop (software PC2500)